Key takeaways
- Megger MIT series covers test voltages up to 10kV (MIT1025). The standard for high-voltage cable and transformer testing; Fluke's highest test voltage is 1000V (1587 FC), covering most LV system applications.
- Fluke's 1587 FC combines a CAT IV 600V true-RMS multimeter with a 1000V insulation tester in one unit. The practical choice for M&E technicians who previously carried two separate instruments.
- Polarisation Index (PI) and Dielectric Absorption Ratio (DAR) (the diagnostic tests that reveal winding condition in motors and transformers), are standard on both Megger MIT series and Fluke 1587 series.
- Megger's heritage in rotating machine testing (motors, generators, transformers) makes it the preferred choice for facilities engineers managing large electrical plant and for electrical contractors doing formal IEE Wiring Regulations testing.
- Both instruments require annual calibration. Test voltage, leakage current measurement, and timer function all drift; Unitest calibrates both brands under its SAC-SINGLAS accreditation.
Why insulation resistance testing matters, and what it actually measures
Insulation resistance is the resistance of the insulating material surrounding electrical conductors. The rubber or XLPE jacket on a cable, the varnished windings in a motor, the dielectric in a transformer. As insulation ages, absorbs moisture, or becomes contaminated by oil, chemicals, or dust, its resistance drops. Eventually it will fail, causing earth faults, nuisance tripping on residual current devices, fire risk, and in the worst cases, electrocution.
Insulation resistance testing applies a high DC voltage to the conductor and measures the tiny leakage current that flows through the insulation to earth or an adjacent conductor. Ohm's law then gives the insulation resistance: a healthy cable or motor winding typically has insulation resistance in the hundreds of megohms to gigohms; a deteriorating winding may drop to tens of megohms; a winding approaching failure may show only a few megohms or less. Regular testing reveals deterioration well before it becomes a fault. It is the electrical equivalent of measuring blood pressure before a stroke, not after.
In Singapore, electrical installations are governed by SS 638, which adopts the requirements of BS 7671 (the IEE Wiring Regulations). SS 638 requires insulation resistance testing as part of initial verification at installation commissioning and periodic inspection and testing thereafter. The test results are recorded on the Schedule of Test Results that accompanies the Electrical Installation Certificate. These become part of the permanent compliance record for the installation. For M&E contractors, facilities engineers, and electrical testing labs, the insulation tester is therefore not just a diagnostic tool: it is a document-generating instrument whose calibration status directly affects the validity of the compliance records it produces.
Megger: the original insulation tester and its heritage
Megger's history begins in the United Kingdom in 1889, when the company introduced the first portable insulation resistance tester. The instrument (hand-cranked, robust, and reliable), became so universally adopted by electrical engineers and contractors that the brand name entered the trade as a generic verb: "to Megger" a cable means to test its insulation resistance, regardless of what instrument is actually used. Megger (now owned by Regula) remains an active brand and the association is not accidental. The company has spent over a century refining instruments that do one thing exceptionally well.
The current MIT series covers a wide range of applications and budgets. The MIT300 is a basic, compact unit suited for routine LV installation checks. The MIT400 and its successor the MIT430 are the mid-range workhorses. Dedicated insulation testers with PI and DAR capability, IP54 weather resistance, and a clear digital display with analogue arc scale for watching resistance stabilise in real time. The MIT510 extends to 5kV test voltage, covering medium-voltage cable testing. At the top of the range, the MIT1025 tests to 10kV and is the standard instrument for formal acceptance testing of medium-voltage cables and power transformers.
The 10kV range is not a specialist curiosity. It is the standard test voltage for 22kV cable systems when the cable's test voltage specification calls for 10kV applied to the installed cable. No Fluke insulation tester comes close to this range. For industrial facilities with medium-voltage switchgear and distribution, or for electrical contractors tendering for utility infrastructure work, Megger's upper MIT series is effectively without a direct competitor from Fluke.
Megger's strengths beyond voltage range include the IP54 weather resistance of the MIT430 and above. A meaningful advantage for contractors working outdoors, in plant rooms, or in humid tropical conditions. The analogue arc scale is a deliberate design choice: resistance values in insulation testing are rarely perfectly stable, and watching the arc settle over 60 seconds or 10 minutes (during a PI test) gives the experienced engineer information that a pure digital readout can obscure.
Fluke 1587 FC: the all-in-one case
Fluke's approach to the insulation tester market is characterised by the insight that many M&E technicians carrying an insulation tester are also carrying a multimeter, and paying for two calibration certificates, two carrying cases, and two sets of test leads. The Fluke 1587 FC is the answer to that observation: a single instrument that combines a 1000V insulation tester with a full CAT IV 600V / CAT III 1000V true-RMS multimeter.
The multimeter side of the 1587 FC is not an afterthought. It measures AC and DC voltage to 1000V, AC and DC current to 10A, resistance, continuity with audible tone, diode test, and capacitance. The 6000-count display with analogue bargraph handles the full range of general electrical measurement a site technician encounters. The CAT IV 600V safety rating (identical to the Megger MIT430's), means it is rated for use at the service entrance and on distribution systems, not just plug circuits.
On the insulation testing side, the 1587 FC offers test voltages of 50V, 100V, 250V, 500V, and 1000V. Insulation resistance measurement range extends to 2000MΩ. PI and DAR tests are built in. The instrument stores up to 99 readings internally and connects wirelessly via Fluke Connect. The Fluke cloud platform for test and measurement records. Readings taken in the field sync to the Fluke Connect app on a smartphone, where they can be tagged to an asset, combined into a measurement summary, and emailed as a PDF report without manual transcription. For contractors who need to produce digital handover documentation for SS 638 compliance, this is a substantial time saving.
The Fluke 1577 is the entry-level variant (test voltage to 500V, no wireless connectivity, lower insulation resistance range), suited for basic LV installation checking where the full 1000V test voltage and wireless features are not required.
The practical limitation of the 1587 FC is clear: its maximum test voltage of 1000V means it is an LV instrument. Any application requiring test voltages above 1kV (medium-voltage cable testing, transformer acceptance testing), is outside its capability. Within the LV world, it covers everything SS 638 requires.
Full specification comparison
The table below compares the Fluke 1587 FC against the Megger MIT430. The two most directly comparable instruments at the mainstream mid-range. The Megger MIT430 is Megger's current entry-to-mid model; higher MIT models (MIT510, MIT1025) extend the voltage range significantly.
| Feature | Fluke 1587 FC | Megger MIT430 |
|---|---|---|
| Test voltage range | 50, 100, 250, 500, 1000V | 50, 100, 250, 500, 1000V |
| Maximum test voltage | 1000V | 1000V (MIT430); up to 10kV (MIT1025) |
| Insulation resistance range | 0.01 MΩ – 2000 MΩ | 0.01 MΩ – 2000 GΩ |
| PI / DAR test | Yes | Yes |
| Continuity test | Yes | Yes |
| Combined multimeter | Yes. Full True RMS multimeter (CAT IV 600V) | No. Dedicated insulation tester only |
| AC/DC voltage measurement | Yes. Full voltage, current, resistance | Voltage measurement only (no current/resistance) |
| CAT safety rating | CAT IV 600V / CAT III 1000V | CAT IV 600V |
| Wireless connectivity | Yes. Fluke Connect compatible | No (MIT430); optional on higher models |
| Display | 6000-count + analogue bargraph | Digital + analogue arc scale |
| IP rating | IP40 | IP54 |
| Weight | 0.52 kg | 0.63 kg |
| Typical price (SG$) | S$1,200 – S$1,500 | S$800 – S$1,200 (MIT430); MIT series S$3,000+ for higher models |
| Calibration interval | 12 months | 12 months |
Two rows in the table warrant closer attention. First, the maximum insulation resistance range: Megger MIT430 measures to 2000 GΩ, while the Fluke 1587 FC measures to 2000 MΩ, a 1000:1 difference. For LV cable and installation testing, this gap rarely matters in practice, because deteriorating insulation that needs attention typically falls well within the Fluke's 2000 MΩ upper limit. Where the difference becomes significant is in formal high-voltage cable acceptance testing, where good-quality HV cables at high test voltages may show very high resistance values that a 2000 MΩ upper limit cannot resolve. Second, the IP54 rating of the Megger MIT430 versus IP40 of the Fluke 1587 FC, in Singapore's humid tropical climate with frequent rain events, the higher ingress protection rating of the Megger is a practical advantage for outdoor or plant room work.
Polarisation Index and Dielectric Absorption Ratio. What they measure and when you need them
A simple insulation resistance test applies the test voltage and records the resistance at a fixed time, typically 60 seconds. This gives a single data point. The Polarisation Index (PI) and Dielectric Absorption Ratio (DAR) tests extend the measurement over time to extract additional diagnostic information from the shape of how the resistance changes.
The PI test applies the test voltage for 10 minutes and compares the resistance at 10 minutes to the resistance at 1 minute. Good insulation shows resistance that continues to rise as polarisation current within the dielectric settles, a PI above 2.0 is generally acceptable; above 4.0 is excellent. Deteriorating insulation, particularly insulation with absorbed moisture or chemical contamination, shows a flatter response where the resistance stabilises or even decreases, a PI below 1.0 is a warning of significant deterioration. IEEE 43 (the standard for insulation resistance testing of rotating machinery) provides the benchmark values.
The DAR test is a faster version of the same principle: it compares resistance at 60 seconds to resistance at 30 seconds. It produces a ratio typically in the range of 1.0 to 1.6 for good insulation. DAR is quicker to run than PI but less sensitive. It is useful for a rapid initial assessment or where waiting 10 minutes per test is impractical.
Both tests are standard on the Fluke 1587 FC and on the Megger MIT430 and above. Where Megger's deeper expertise shows is in larger plant applications: formal acceptance testing of motors above 1MW to IEC 60034, transformer acceptance testing to IEC 60076, and generator commissioning. In these contexts, the Megger dedicated insulation tester is the preferred instrument. Partly for its extended resistance range at high test voltages, partly for the heritage and familiarity of inspectors and commissioning engineers who have used Megger instruments for these applications for decades.
For M&E contractors doing routine SS 638 installation testing and motor maintenance in commercial buildings, the PI/DAR capability of the Fluke 1587 FC is fully adequate. The question of "dedicated Megger vs all-in-one Fluke" for PI/DAR applications depends on the application scale, not on the presence or absence of the test function itself.
Applications in Singapore: M&E contractors vs facilities management vs electrical testing labs
Three distinct user segments in Singapore approach insulation testing with different requirements, and each benefits from a different instrument choice.
M&E contractors: new installation testing to SS 638
An M&E contractor testing a new LV installation before handover needs to verify insulation resistance of every circuit, record the results on the Schedule of Test Results, and produce documentation that satisfies the SP Services or Building and Construction Authority (BCA) inspection process. The test voltages required under SS 638 for LV systems (500V for circuits rated to 500V, 1000V for circuits rated to 1000V), are fully within the Fluke 1587 FC's range. The Fluke Connect wireless logging reduces documentation time significantly on large installations with many circuits. For contractors who also carry a multimeter for fault-finding during the same site visit, the 1587 FC's combined functionality means one calibration certificate covers both instruments' functions. For M&E contractors working primarily on LV commercial and residential installations, the Fluke 1587 FC is the practical winner.
Facilities management: ongoing preventive maintenance of motors and plant
A facilities engineer managing a large commercial building, hospital, or industrial plant runs insulation testing as part of a preventive maintenance programme. Typically annually on critical motors, air handling units, transformer feeders, and switchgear. The Megger MIT430 is the preferred dedicated instrument here: its IP54 rating handles plant room humidity and occasional water ingress better than the Fluke's IP40 rating, its analogue arc scale helps the engineer watch resistance develop during a PI test, and the dedicated-instrument design means there are no multimeter functions to switch between when running a systematic testing programme. For facilities with any medium-voltage equipment (22kV switchgear, HV distribution transformers), the higher MIT series (MIT510 or MIT1025) is essential and the Fluke 1587 FC is not an alternative.
Electrical testing labs and specialist contractors
An electrical testing lab or specialist high-voltage contractor carrying out cable acceptance testing, transformer commissioning, or generator acceptance testing works at test voltages where Fluke has no product. A 22kV XLPE cable run requires a 10kV insulation resistance test; a 6.6kV motor winding requires a 5kV test. The Megger MIT510 and MIT1025 are the instruments of choice for this segment, and Fluke simply does not compete in it. If your work regularly requires test voltages above 1kV, the instrument decision is made before you compare features.
Insulation resistance calibration. What is checked and why it drifts
Insulation testers are measurement instruments, and like all measurement instruments, their accuracy drifts over time. Understanding what drifts helps explain why annual calibration is necessary and what a calibration laboratory actually checks.
The high-voltage generator is the first element to verify. An insulation tester applies a nominally stable DC voltage (500V, 1000V, or higher), across the insulation under test. In practice, the generator output can drift: the displayed test voltage may say 500V but the actual output under load conditions may be 460V or 540V. Because insulation resistance is strongly dependent on the applied voltage (particularly at marginal resistance values), an inaccurate test voltage produces systematically incorrect resistance readings. A calibration laboratory checks the test voltage output at each setting under representative load conditions, not just at no load.
The current measurement circuit is the second element. The insulation resistance is calculated from the measured leakage current at the known test voltage. If the current measurement circuit drifts, resistance readings drift proportionally. Calibration laboratories verify the resistance measurement accuracy by connecting the instrument to precision reference resistors (typically at multiple points across the resistance range), and checking that the instrument reads within its stated accuracy specification.
The PI/DAR timer is the third element. The PI calculation depends on accurate timing of the 10-minute test: if the timer runs fast or slow, the resistance value recorded at "10 minutes" is not actually taken at 10 minutes, and the PI ratio is incorrect. Calibration includes verifying the timer function.
What the calibration certificate should state: the test voltages verified (each setting), the resistance ranges checked (with reference resistor values and expanded uncertainty), and confirmation that the PI/DAR timer function was verified. A certificate that shows only a pass/fail without stating the measurement uncertainty of the calibration itself does not meet the requirements of ISO 9001 clause 7.1.5 for instruments used in quality-critical measurement.
The practical implication of an uncalibrated insulation tester is significant. An engineer who tests a motor winding, reads 150 MΩ at 500V, and judges the winding acceptable against a 100 MΩ minimum specification has made a decision that is only as valid as the accuracy of the instrument. If the actual test voltage was 420V (not 500V), the equivalent reading at 500V would be lower than displayed, and the motor may actually be marginal. Calibration evidence is not a bureaucratic requirement; it is the basis for trusting the measurement.
Calibrate your Fluke or Megger insulation tester. Traceable certificate for compliance
Unitest calibrates insulation testers (test voltage, resistance ranges, PI/DAR timer) against NMC-traceable references. SAC-SINGLAS accredited certificates accepted for SS 638 compliance and ISO 9001 audits.
Megger vs Fluke for specific Singapore applications
Four common scenarios with clear instrument recommendations:
(a) New LV installation testing under SS 638
Both the Fluke 1587 FC and Megger MIT430 are fully adequate. The SS 638 test voltages (500V and 1000V for LV systems) are within both instruments' ranges, and both produce results that can be recorded on the Schedule of Test Results. The Fluke 1587 FC's Fluke Connect wireless logging offers a practical advantage for contractors wanting digital documentation. If the contractor already owns a separate multimeter, the dedicated Megger MIT430 may be the cleaner choice; if they are equipping from scratch, the Fluke 1587 FC's combined functionality offers better total cost of ownership.
(b) Motor preventive maintenance in food manufacturing or industrial plant
Megger MIT430 is the preferred instrument. The IP54 rating handles the humidity and potential water splash in production environments better than the Fluke's IP40. The dedicated instrument design makes running a systematic PI test programme more efficient than switching between multimeter and insulation modes on a combined instrument. Annual calibration certificates documenting the test voltage and resistance accuracy should be retained as evidence for ISO 9001 clause 7.1.5 compliance and any HSA GMP audit of the maintenance programme.
(c) 22kV cable testing at an industrial facility or utility substation
Megger MIT510 (5kV) or MIT1025 (10kV) only. There is no Fluke alternative for medium-voltage cable testing. The required test voltage for 22kV XLPE cables is typically 10kV applied to the installed cable after jointing and before energisation. This test cannot be performed with any Fluke insulation tester in the current range. The Megger MIT1025 is the standard instrument for this application, used by electrical contractors, power utilities, and testing consultants across Singapore and the region.
(d) General M&E site work with one instrument
Fluke 1587 FC. The combined multimeter and insulation tester reduces kit weight, cost, and calibration overhead. For an M&E technician whose daily work involves fault-finding, continuity testing, voltage measurement, and periodic insulation tests on LV circuits, the 1587 FC is the most practical single instrument available. It handles everything SS 638 requires on LV systems while doubling as a full general-purpose multimeter.
What to look for when buying an insulation tester. Avoiding the cheap alternatives
The market is well-stocked with unbranded insulation testers at S$50–200, typically sourced from generic Asian manufacturers and sold on e-commerce platforms with specifications that look credible at first glance: "1000V test voltage, 2000 MΩ range, PI/DAR capable." The reality is consistently disappointing when these instruments arrive in a calibration laboratory.
The fundamental problem is that the test voltage specification is typically measured at no load. The open-circuit output of the HV generator with nothing connected. Under the actual load of an insulation resistance measurement (which draws a small leakage current), the generator output collapses, often to 70–80% of the rated voltage. A tester nominally set to 500V may be applying 380V to the cable under test. The resistance reading it produces is therefore not comparable to the specification limit established with a calibrated instrument at a known 500V.
The resistance measurement accuracy of cheap testers is also consistently poor across the full range. Particularly at the high-resistance end where good insulation actually reads. Linearity is poor, and the calibration traceability is either absent or claimed through chains that do not withstand examination.
For any organisation operating under ISO 9001, GMP, or any other management system that treats insulation testers as controlled measurement equipment, a cheap unbranded instrument fails at the first hurdle: it cannot be meaningfully calibrated against traceable references because its performance is too unstable and variable to establish a valid calibration uncertainty. The compliance value of the certificate it generates is nil.
The practical guidance is straightforward: for any insulation testing that will be used in compliance documentation (SS 638 handover records, motor maintenance logs, transformer acceptance certificates), buy an instrument from Fluke, Megger, Kyoritsu, Hioki, or Metrel. Obtain it from an authorised distributor. Register it in your calibration programme from day one and send it for SAC-SINGLAS accredited calibration annually. The instrument cost over five years is far less than the cost of a single major non-conformance triggered by suspect measurement data.
The calibration register for insulation testers. Practical compliance
Insulation testers used in electrical safety compliance (SS 638 installation testing, motor maintenance programmes, transformer acceptance), are measurement instruments under ISO 9001 clause 7.1.5. They must be identified, calibrated at defined intervals, protected from damage, and have their calibration status traceable. In practice this means maintaining a calibration register that documents each instrument's identity and calibration history.
A compliant calibration register entry for an insulation tester should include: the asset ID or serial number; the make and model (e.g. Megger MIT430, serial 12345678); the test voltage settings covered by the calibration; the calibration date and the certificate reference number; the calibration laboratory and its accreditation number; and the next calibration due date. For instruments where the calibration covers multiple test voltages or multiple resistance ranges, the register should confirm that all the ranges actually used in your compliance testing are covered by the certificate. Accreditation is scope-specific, and a certificate that covers only 500V and 1000V does not cover a 250V test performed for a specific circuit type.
The recommended calibration interval is 12 months. Fluke and Megger both specify this interval for their insulation tester range. For instruments used heavily (multiple daily measurements in harsh environments), a shorter interval or a post-event check (after a significant drop, a severe electrical event, or any visible damage) is prudent.
The risk of using an overdue insulation tester on a project requiring compliant handover documentation is not merely theoretical. If a project's SS 638 Schedule of Test Results is reviewed during a building inspection or regulatory audit and the insulation tester's calibration certificate is found to be expired, the validity of every insulation resistance result on that schedule is in question. Rectifying this after the fact may require repeat testing, at additional cost and possible delay to project handover. Maintaining current calibration certificates is cheaper insurance than any scenario that follows from lapsed ones.
Frequently asked questions
For low voltage (LV) cable and installation testing in Singapore under SS 638 (which adopts BS 7671), the standard test voltage for circuits rated up to 500V is 500V DC. For circuits rated above 500V and up to 1000V, a test voltage of 1000V DC is used. Both Fluke 1587 FC and Megger MIT430 cover these test voltages fully. For medium-voltage cable systems above 1kV (22kV distribution cables, 6.6kV motor feeders), a higher test voltage is required, typically 2.5kV to 10kV, and only the Megger MIT500 or MIT1025 series provides this range.
A Polarisation Index (PI) above 2.0 is generally considered acceptable for motors and rotating machines. A PI between 1.0 and 2.0 indicates marginal insulation condition and warrants closer monitoring or investigation. A PI below 1.0 is a warning sign of significant insulation deterioration. The motor should be investigated before returning to service. These thresholds are drawn from IEEE 43, the standard for insulation resistance testing of rotating machinery. Note that very high-resistance windings in new or dry motors may give inconclusive PI results, in those cases, Dielectric Absorption Ratio (DAR) may be more informative as a rapid indicator.
The Fluke 1587 FC covers all low-voltage insulation testing under SS 638 / BS 7671. It handles test voltages from 50V to 1000V and includes PI and DAR testing. For the vast majority of M&E contractors and facilities engineers working on LV systems in Singapore, the 1587 FC is entirely adequate. The only applications it cannot cover are medium-voltage cable testing (above 1000V test voltage) and transformer acceptance testing at voltages above 1kV. For those applications, a Megger MIT510 (5kV) or MIT1025 (10kV) is required. A range that the Fluke product line does not offer.
The recommended calibration interval for insulation testers is 12 months. Both Fluke and Megger specify a 12-month interval for their insulation tester ranges. For instruments used in safety-critical applications (commissioning testing of new LV installations, acceptance testing of motors and transformers), calibrating annually against traceable references and obtaining a SAC-SINGLAS accredited certificate is the standard expectation. If an instrument is dropped, subjected to a significant electrical event, or shows readings inconsistent with expectations, it should be returned for calibration and inspection before further use regardless of the scheduled interval.
There is no technical difference. The term "Megger test" is an informal trade name for an insulation resistance test, derived from the Megger brand name in the same way that "Hoovering" refers to vacuuming regardless of the machine's brand. An insulation resistance test applies a known DC voltage across insulation and measures the resulting leakage current to calculate resistance. When an electrician says they will "Megger the cable," they mean they will perform an insulation resistance test. Any calibrated insulation tester (Fluke, Megger, Kyoritsu, Hioki, or Metrel), performs the same measurement.
Yes. Unitest calibrates Megger insulation testers including the MIT300, MIT400, MIT430, MIT510, and MIT1025 series under its SAC-SINGLAS accreditation. Calibration covers test voltage output accuracy at each test voltage setting, insulation resistance measurement accuracy across the specified ranges, continuity test function, and the PI/DAR timer where applicable. Certificates are issued with full NMC traceability and stated measurement uncertainty, meeting the requirements of ISO 9001 clause 7.1.5 and SS 638 compliance documentation. Fluke 1587 FC, 1577, and related models are also calibrated under the same accreditation.
Cheap insulation testers (typically unbranded units at S$50–200), fail calibration for a consistent set of reasons. First, the high-voltage generator output is rated at no load: under the load of an actual insulation measurement, the test voltage collapses well below the stated value, meaning a reading of 200 MΩ at "500V" may actually be a measurement taken at 380V or less. Second, the resistance measurement circuit has poor linearity and accuracy across the full range, particularly at high resistance values. Third, PI/DAR timers, where present, are inaccurate. The result: a reading from a cheap tester cannot be meaningfully compared to a compliance specification limit, and no accredited certificate can be issued against it.
Insulation tester calibration. Fluke and Megger both covered
Unitest calibrates insulation testers to cover test voltage output, resistance measurement, and PI/DAR timer. SAC-SINGLAS accredited certificates, NMC traceable.
Verifiable at sac.gov.sg · Acc. No. LA-2023-0845-C

