SAC-SINGLAS Accredited ISO/IEC 17025 Acc. No.LA-2023-0845-C Traceable to Singapore's NMC View accreditation
Brand Comparison

Fluke vs Kyoritsu Insulation Tester: Which Is Better for Singapore Electrical Contractors?

Insulation resistance testers (megohmmeters) from Fluke and Kyoritsu are both widely used by Singapore electrical contractors, EMA-licensed electricians, and industrial maintenance teams. Fluke's 1550C and 1587FC series are the premium choice; Kyoritsu's 3125A and 3132A cover similar ranges at significantly lower cost. This comparison focuses on what matters for SS 638 (Code of Practice for Electrical Installations), EMA compliance testing, and routine site testing in Singapore's tropical environment.

24 June 202611 min readBrand Comparison
Insulation resistance testing equipment for Singapore electrical contractors. Fluke and Kyoritsu megohmmeters
The short answer For EMA-licensed electricians and electrical contractors carrying out SS 638 compliance testing in Singapore, the Kyoritsu 3125A or 3132A provides entirely adequate performance for routine insulation resistance testing at a significantly lower cost than the Fluke 1550C. Choose Fluke if you need medium-voltage cable testing (5kV output), automated PI/DAR analysis, or Fluke Connect wireless data transfer for multi-site reporting. Both brands require annual SAC-SINGLAS accredited calibration for the calibration certificate to be accepted in formal compliance documentation.

Key takeaways

  • Singapore's tropical climate (85–95% relative humidity) suppresses apparent insulation resistance readings. Both brands include temperature correction, but field readings should always be noted alongside ambient temperature and humidity conditions.
  • Fluke 1550C provides up to 5kV test voltage and measures to 2TΩ. Essential for medium-voltage cable testing and transformer insulation testing; Kyoritsu 3125A provides 5kV and 4TΩ measurement range at a lower price point.
  • Kyoritsu's 3132A (1kV, 60GΩ) is the appropriate and cost-effective choice for the vast majority of SS 638 routine testing on LV installations , 500V test voltage covers most LV circuit insulation requirements.
  • Both instruments are IEC 61557-2 compliant, which defines measurement accuracy and safety requirements for insulation resistance testers. Do not use non-compliant instruments for SS 638 compliance documentation.
  • Annual calibration is mandatory for both brands when used in formal compliance testing; insulation resistance calibration at high megohm ranges requires specialised precision resistor standards not available at general-purpose calibration labs.

Why Insulation Testing Matters for Singapore Electrical Installations

Insulation failures are a leading cause of electrical fires and electrocution in Singapore. The insulating material surrounding electrical conductors (the PVC or XLPE jacket on a cable, the varnish coating on motor windings, the dielectric in a transformer), forms the barrier between energised conductors and the human beings and building fabric that surround them. As insulation ages, absorbs moisture, or is damaged by heat, mechanical stress, or chemical contamination, its electrical resistance falls. Eventually it fails, creating earth faults, nuisance tripping on residual current devices, and in the worst cases, fire and electrocution.

Insulation resistance testing applies a known DC voltage across the insulation and measures the tiny leakage current that flows through it to calculate resistance. Healthy insulation in a modern LV installation reads in the hundreds of megohms to gigohms range. Deteriorating insulation may fall to tens of megohms. Insulation approaching failure may show only a few megohms or less. Regular testing allows maintenance teams to identify declining insulation condition well before a fault occurs. It is predictive maintenance in its most direct form.

SS 638 (Singapore Standard: Code of Practice for Electrical Installations) sets the framework for when insulation testing is required. New electrical installations must be tested before energisation and the results recorded on a Schedule of Test Results signed by the responsible licensed electrical worker. Installations must be retested before re-energisation after significant repair or modification. Periodic inspection and testing of existing installations (typically at intervals of one to five years depending on the installation type), also requires insulation resistance measurement. The Schedule of Test Results and associated certificates form a legally required compliance record.

EMA (Energy Market Authority) licensing requirements reinforce this framework: SP Services and EMA require insulation resistance test certificates signed by EMA-licensed electrical workers as part of the approval process for new connections and for certain modification works. The calibration status of the instrument used to generate those certificates is therefore directly tied to the legal validity of the documentation.

What insulation resistance testing actually measures is the combined resistance of the insulation between each conductor and all other conductors and between each conductor and earth, with all circuit breakers closed and all equipment disconnected. The result indicates whether the installed wiring has adequate insulation integrity for safe energisation.

Understanding Insulation Tester Specifications

Insulation resistance testers differ in two fundamental parameters: the test voltage they apply and the measurement range they can report. Understanding these helps match the instrument to the application.

Test voltage selection is application-driven. The appropriate test voltage depends on the rated voltage of the circuit or equipment being tested: 250V DC is used for SELV circuits and structured cabling such as Cat5/6; 500V DC is the standard for LV installations rated up to 1kV; 1000V DC is used for motors, transformers, and switchgear rated above 500V; 2500V DC covers medium-voltage cables up to approximately 6.6kV systems; 5000V DC is appropriate for medium-voltage cables and transformers at higher voltage ratings. Using a test voltage higher than the equipment's insulation rating risks damaging new insulation, particularly in XLPE cables where excessive voltage can cause tree-tracking.

Measurement range is expressed in megohms (MΩ), gigohms (GΩ), or teraohms (TΩ). A higher measurement range allows the instrument to resolve very high insulation resistance values without the reading simply pegging at the maximum. Useful for assessing very high-quality insulation on new cable runs or for detecting subtle differences in insulation condition between test periods. In practice, most LV routine testing produces readings well within the range of any quality insulation tester; the upper range matters most for high-voltage cable acceptance testing and transformer insulation assessment.

Polarisation Index (PI) is the ratio of the 10-minute insulation resistance reading to the 1-minute reading. Good, dry insulation shows a rising resistance over time as polarisation currents settle, giving a PI above 2.0. Contaminated, moisture-laden, or deteriorated insulation shows a flat or falling response, with PI values below 1.0 indicating significant problems. PI testing is standard practice for motors, generators, and transformer windings where a single-point reading is insufficient for condition assessment.

Dielectric Absorption Ratio (DAR) compares the 60-second to the 30-second insulation resistance reading. A faster test than PI but less sensitive. DAR is useful for a rapid initial assessment where a full 10-minute PI test is impractical.

IEC 61557-2 is the international standard defining accuracy and safety requirements for insulation resistance testers. It specifies the minimum acceptable accuracy of the resistance measurement and the test voltage output, and sets the safety category requirements. Both Fluke and Kyoritsu explicitly reference IEC 61557-2 compliance in their product specifications. This should be verified before purchasing any insulation tester intended for use in formal compliance testing. Non-compliant instruments should not be used for SS 638 compliance documentation.

Fluke 1550C and 1587FC. The Premium Choice for Singapore Contractors

Fluke's insulation tester range occupies the premium tier of the market, combining engineering quality with practical features designed for professional contractors and facilities engineers. The two models most relevant to Singapore electrical work are the 1550C and the 1587FC.

The Fluke 1550C is the dedicated high-voltage insulation tester in Fluke's range. It provides test voltages of 500V, 1kV, 2.5kV, and 5kV, with a measurement range extending to 2TΩ. At 5kV test voltage, it covers medium-voltage cable testing and transformer insulation assessment. Applications that go beyond the capability of standard LV instruments. Automated PI, DAR, and step voltage tests are built in, allowing systematic condition assessment of motors, transformers, and cable systems without manual timing. The safety rating is CAT IV 600V, appropriate for testing at the service entrance and distribution level. IP40 ingress protection provides basic dust resistance. Battery life is approximately seven hours in continuous test mode. Warranty is three years. The Fluke 1550C includes automatic discharge of the capacitance of the wiring or equipment under test after the measurement is complete. A critical safety feature when working on longer cable runs or large motor windings, which can store significant charge at 5kV.

The Fluke 1587FC takes a different approach: it combines a 1kV insulation tester with a full true-RMS multimeter in a single instrument. Test voltages run from 50V to 1000V, covering all LV insulation testing applications. The insulation resistance measurement range extends to 2000MΩ. The multimeter side provides AC and DC voltage to 1000V, current to 10A, resistance, continuity, capacitance, and diode test. CAT III 1000V rated for panel work. For field electricians who previously carried both a multimeter and an insulation tester, the 1587FC replaces both instruments and consolidates to a single calibration certificate. Automatic discharge is included on both the 1587FC and the 1550C.

Fluke Connect wireless data transfer via Bluetooth to the Fluke Connect smartphone app is a significant practical advantage for contractors managing multiple sites and needing to compile digital test records. Readings taken in the field sync automatically, can be tagged to assets, and exported as PDF reports without manual transcription. A meaningful time saving on large installations with many circuits to document. Singapore's trend towards electronic handover documentation makes this increasingly relevant.

Fluke maintains an authorised calibration and service network in Singapore, providing calibration certificates with fast turnaround. Both the 1550C and 1587FC are widely supported by accredited calibration laboratories in Singapore including Unitest Instruments.

Kyoritsu 3125A and 3132A. The Value Choice for Routine Testing

Kyoritsu (KEW) has manufactured electrical test instruments in Japan since 1940. The brand is well-established across Asia and particularly well-regarded in Singapore's electrical contracting community for producing reliable, honest instruments at lower price points than the premium Western brands. Quality control is consistent and the instruments perform reliably in field conditions.

The Kyoritsu 3125A is the high-end model in Kyoritsu's insulation tester range and directly competes with the Fluke 1550C in capability. It provides test voltages of 500V, 1kV, 2.5kV, and 5kV, with a measurement range of 4TΩ. Notably exceeding the Fluke 1550C's 2TΩ upper limit. Automated PI, DAR, and step voltage tests are included. The safety rating is CAT IV 600V. Significantly, the 3125A carries an IP54 ingress protection rating (dust-tight and splash-proof), versus the Fluke 1550C's IP40. In Singapore's humid tropical climate and on exposed construction sites subject to rainfall, IP54 is a meaningful practical advantage. The lockable on-switch prevents accidental activation. Battery life is approximately 200 measurements. At typical Singapore market prices, the 3125A comes in 30–40% lower than the comparable Fluke 1550C.

The Kyoritsu 3132A is the standard LV model. Test voltages of 250V, 500V, and 1kV, measurement range to 60GΩ, simpler operation without automated PI/DAR timing, and CAT IV 600V safety rating with IP54 protection. It is the appropriate instrument for the vast majority of SS 638 routine testing on LV installations and significantly cheaper than the Fluke 1587FC. For electrical contractors whose work is primarily routine LV circuit testing (new installation commissioning, periodic inspection), the 3132A does the job without unnecessary complexity.

Both Kyoritsu models are explicitly IEC 61557-2 compliant, meeting the accuracy and safety requirements of the standard. Kyoritsu instruments are available through authorised distributors in Singapore, and calibration support is available through specialist laboratories including Unitest Instruments, whose SAC-SINGLAS accreditation scope covers Kyoritsu insulation testers.

The absence of wireless data transfer on Kyoritsu instruments (neither the 3125A nor 3132A includes Bluetooth connectivity) is the most significant functional gap relative to the Fluke range. Contractors who rely on digital test record management will need to record readings manually or transfer them via USB or direct download. For contractors whose documentation workflow is paper-based or who use their own field reporting app, this is not a disadvantage in practice.

Head-to-Head Comparison

The table below compares all four instruments across the parameters most relevant to Singapore electrical contractors and EMA-licensed electricians.

Parameter Fluke 1550C Fluke 1587FC Kyoritsu 3125A Kyoritsu 3132A
Test voltages (V) 500/1k/2.5k/5k 50/100/250/500/1000 500/1k/2.5k/5k 250/500/1000
Max measurement range 2TΩ 2,000MΩ 4TΩ 60GΩ
PI/DAR automated Yes No Yes No
Step voltage test Yes No Yes No
Safety rating CAT IV 600V CAT III 1000V CAT IV 600V CAT IV 600V
IP rating IP40 IP40 IP54 IP54
Wireless data Fluke Connect Fluke Connect No No
Battery life 7hrs (test mode) 400hrs 200 measurements 400 measurements
Approx. price (SGD) $1,800–$2,200 $700–$900 $1,100–$1,400 $400–$600
Best for MV cables, comprehensive Field, dual function MV cables, value LV routine, budget

Several rows deserve closer attention. The Kyoritsu 3125A's 4TΩ measurement range exceeds the Fluke 1550C's 2TΩ at a lower price, for contractors assessing very high-quality insulation on new cable installations, where readings may approach the upper limit of lesser instruments, this is a genuine advantage. The IP54 rating of both Kyoritsu models against IP40 on both Fluke models is a consistent pattern: Kyoritsu prioritises site weather resistance more than Fluke does at each comparable tier. The absence of Fluke Connect on Kyoritsu instruments is the clearest differentiator favouring Fluke for contractors whose documentation workflow depends on digital data capture.

Tropical Climate. The Singapore-Specific Consideration

Singapore's climate presents a challenge that does not appear in the technical specifications of any insulation tester. Ambient relative humidity in Singapore is 72–90% on most days and reaches 100% during rainfall. Overnight temperatures typically fall to 25–27°C before rising to 31–34°C in the afternoon, creating a daily condensation cycle in enclosed electrical spaces. Conduits, cable trays, junction boxes, and distribution boards.

The effect on insulation resistance readings is substantial. Moisture in cable conduits, on cable surfaces, and absorbed into cable insulation provides a partial conductive path in parallel with the cable's true insulation resistance. This reduces the apparent measured resistance, sometimes dramatically. A cable that reads 500MΩ in a dry, climate-controlled environment in a temperate country may read 50MΩ on a Singapore construction site in humid conditions without any actual fault in the insulation. Contractors unfamiliar with this effect may incorrectly flag compliant installations as having insulation problems, or conversely, may set inappropriately low acceptance thresholds that allow genuinely marginal insulation to pass.

Both Fluke and Kyoritsu instruments include temperature correction, applying a correction factor based on the measured or entered ambient temperature. The standard reference temperature for insulation resistance comparison is 20°C. In Singapore's typical ambient of 28–32°C, readings require correction for any meaningful cross-period comparison. Temperature correction tables and correction factors are published in IEEE 43 and in the instrument manufacturers' documentation.

Humidity correction is a separate consideration not directly performed by the instruments themselves. Best practice for Singapore site testing is to always record ambient temperature and relative humidity alongside insulation resistance readings; to test after the installation has been energised for some time (energisation generates heat that drives moisture out of enclosed spaces); to use a dehumidifier in enclosed switchrooms or cable chambers before testing when readings appear anomalously low; and to note in test records any testing carried out within 24 hours of heavy rainfall, as rainfall events suppress insulation resistance readings even in well-installed cable systems.

In terms of performance in humidity, both Fluke and Kyoritsu instruments perform equally. Neither has a measurement circuit advantage in high-humidity conditions. The IP54 rating of the Kyoritsu 3125A and 3132A gives them a marginal practical advantage in exposed site conditions where the instrument itself may be subject to rain splash or condensation on its housing, but this does not affect the quality of the insulation measurement.

SS 638 Minimum Insulation Resistance Requirements

Understanding the minimum requirements of SS 638 helps clarify which instrument is appropriate for which application. SS 638 specifies insulation resistance testing of new LV installations with all conductors connected together and tested between the bundle and earth. The minimum acceptable result is 1MΩ between each conductor (or all conductors connected) and earth. In practice, this is a floor, not a target.

New LV installations of reasonable quality should read significantly above the 1MΩ minimum. Values above 100MΩ are typical for new wiring in good condition. Readings below 10MΩ on new work should prompt investigation and remediation even if they technically exceed the minimum requirement, because an installation that starts at 8MΩ will deteriorate rapidly in Singapore's climate to below the minimum. The 1MΩ minimum represents insulation that is already marginally functional, not insulation that is in good condition.

Test voltage selection per SS 638 follows the circuit rating: 500V DC for circuits rated up to 500V, and 1000V DC for circuits rated above 500V and up to 1000V. Both the Kyoritsu 3132A and the Fluke 1587FC cover these test voltages fully, which is why either is adequate for the majority of LV installation testing. Using higher test voltages than specified by SS 638 is not recommended. Excessive test voltages may damage new insulation, particularly XLPE, through partial discharge mechanisms.

Motor insulation testing typically applies higher test voltages depending on the motor's voltage rating. Motors rated above 1kW are generally tested at 1000V; large motors at 2500V or 5000V depending on their voltage class. For motor testing programmes, the Fluke 1550C or Kyoritsu 3125A (both 5kV capable) are the appropriate instruments. Cable insulation testing uses the test voltage appropriate to the cable's rated voltage, tested between each pair of conductors and between each conductor and earth. A systematic process that takes time on large installations and benefits from the higher measurement range and automated PI/DAR capability of the 1550C or 3125A.

Calibration Requirements for Insulation Testers

Calibration of insulation testers is more technically demanding than calibration of general-purpose multimeters. A multimeter's resistance measurement function typically operates to hundreds of kilohms at most; an insulation tester must be accurately calibrated across a range from 1MΩ to teraohms. Precision resistor standards at those resistance levels (the reference standards used to verify the tester's accuracy), are specialised and expensive, and not available at general-purpose calibration laboratories.

SAC-SINGLAS accreditation scope matters when selecting a calibration laboratory for insulation testers. The accreditation certificate held by a laboratory defines the specific measurement parameters and ranges for which they are accredited. A laboratory accredited for electrical calibration may be accredited for DC resistance to 100kΩ, which is irrelevant for insulation tester calibration. Confirm explicitly that the laboratory's accreditation scope covers insulation resistance measurement at the ranges used in your work. Typically 100MΩ, 1GΩ, and 10GΩ are the relevant reference points for LV routine testing, with higher ranges required for 5kV instruments.

Test voltage accuracy is the second element requiring calibration. An insulation tester that applies 480V instead of 500V DC to the cable under test produces systematically incorrect resistance readings, because insulation resistance is voltage-dependent, the reading at 480V is not directly comparable to the specification limit established at 500V. Test voltage output must be verified at each test voltage setting under representative load conditions, not just at open circuit (no-load) voltage which is always within specification and tells you nothing about the instrument's behaviour under actual test conditions. A thorough calibration laboratory checks test voltage under load.

Annual calibration is the standard recommendation for both Fluke and Kyoritsu instruments used in formal SS 638 compliance testing. Both manufacturers specify a 12-month calibration interval for their insulation tester ranges. For instruments used in safety-critical applications (commissioning testing, motor maintenance programmes, formal compliance records), annual calibration against SAC-SINGLAS accredited references is the minimum acceptable standard.

The risk of using an out-of-tolerance insulation tester is not merely theoretical. If an instrument is found to be reading out of tolerance at its annual calibration, all insulation resistance results generated since the previous in-tolerance calibration are of uncertain validity. In regulated industries (ISO 9001, GMP, or any inspection body reviewing SS 638 compliance records), this may trigger a requirement to repeat testing on all affected installations. Maintaining current calibration certificates and acting immediately when an instrument returns out-of-tolerance is far cheaper insurance than the downstream cost of invalidated test results.

Insulation Tester Calibration

Calibrate Your Insulation Tester to SAC-SINGLAS Standards

Unitest Instruments provides SAC-SINGLAS accredited calibration for Fluke and Kyoritsu insulation resistance testers. Our calibration scope explicitly covers insulation resistance measurement from 1MΩ to 10GΩ and test voltage accuracy. The parameters required for SS 638 compliance documentation.

Which Should You Choose?

Four distinct use cases, four clear recommendations.

Choose Fluke 1587FC if:

You are a field electrician who needs one tool for both insulation testing and general electrical measurement. The 1587FC eliminates the need to carry a separate multimeter and consolidates your calibration overhead to a single certificate. Fluke Connect data logging is a practical advantage if your site documentation workflow requires digital records. The CAT III 1000V rating on the multimeter function makes it suitable for panel work. For LV installation commissioning under SS 638, the 1587FC covers every required test voltage. Note the IP40 rating, in very wet site conditions, keep it in its case when not in active use.

Choose Fluke 1550C if:

Your work includes medium-voltage cable and transformer testing requiring 5kV test voltage, or formal test programmes requiring automated PI and step voltage tests. The Fluke Connect wireless capability justifies the premium if you are managing multi-site testing programmes that benefit from centralised digital data management. The 1550C's established position in Singapore's calibration and service network ensures fast turnaround on calibration certificates. If budget is not a constraint and you need 5kV capability with wireless reporting, the 1550C is the obvious choice.

Choose Kyoritsu 3132A if:

Your primary work is routine LV installation testing to SS 638 and you are budget-conscious. The 3132A covers 250V, 500V, and 1000V test voltages. All that SS 638 requires for LV systems. IP54 ingress protection makes it appropriate for outdoor and exposed site conditions where the Fluke IP40 rating is less suitable. For contractors who do not require automated PI/DAR or wireless data transfer, the 3132A delivers compliant results at significantly lower instrument and calibration cost than Fluke alternatives.

Choose Kyoritsu 3125A if:

You need 5kV output capability for medium-voltage cable or motor testing but want to keep instrument cost lower than the Fluke 1550C. The 3125A's 4TΩ measurement range exceeds the 1550C's 2TΩ. A genuine advantage when assessing very high-quality insulation on new cable installations. IP54 protection is superior to the equivalent Fluke for wet environments. Automated PI, DAR, and step voltage tests are included. For contractors whose work occasionally includes MV testing but whose main volume is LV routine work, the 3125A provides maximum capability at a more accessible price point.

Frequently asked questions

Which insulation tester is better for EMA compliance testing in Singapore?

For the vast majority of EMA-required insulation resistance testing on LV installations (up to 1000V), the Kyoritsu 3132A or 3125A is entirely adequate and costs significantly less than the equivalent Fluke model. Both brands are IEC 61557-2 compliant and produce test results acceptable for SS 638 compliance documentation. Provided the instrument has a current SAC-SINGLAS accredited calibration certificate. The brand is less important than the calibration status.

What test voltage should I use for LV insulation testing in Singapore?

SS 638 specifies 500V DC for circuits operating up to 500V, and 1000V DC for circuits above 500V up to 1000V rated. For standard 230V/400V LV installations in Singapore, 500V is the correct test voltage. Using a higher test voltage than specified is not recommended. It may stress new insulation unnecessarily and produce misleadingly high readings on aged cables. Always check the circuit rating before selecting test voltage.

How does Singapore's tropical humidity affect insulation resistance readings?

High humidity suppresses insulation resistance readings. The moisture content of cable insulation and conduit surfaces provides a partial conductive path that reduces the measured resistance. A cable that reads 500MΩ in a climate-controlled environment may read 50–100MΩ on a Singapore construction site in humid conditions. Both Fluke and Kyoritsu instruments include temperature correction, but humidity correction is a separate consideration. Always record ambient conditions alongside test readings, and retest if readings are unexpectedly low.

How often do insulation testers need calibration?

Annual calibration is the standard recommendation for insulation testers used in formal compliance testing. If the instrument is dropped, reads anomalous values, or shows visible damage to test leads (which contribute to measurement accuracy), immediate recalibration is warranted. The calibration must be performed by a SAC-SINGLAS accredited laboratory with explicit scope for insulation resistance calibration at the relevant ranges.

What insulation resistance reading is acceptable for new LV installations in Singapore?

SS 638 sets a minimum of 1MΩ between conductors and between conductors and earth. However, this is a floor, not a target. A new LV installation of reasonable quality should read significantly higher. Values above 100MΩ are typical for new wiring; readings below 10MΩ on new work warrant investigation even if they exceed the 1MΩ minimum. The PI (Polarisation Index) provides additional diagnostic value: PI > 2 indicates good insulation condition.

What is the difference between PI (Polarisation Index) and DAR (Dielectric Absorption Ratio)?

Both PI and DAR compare insulation resistance readings taken at different time intervals to assess insulation condition. PI is the ratio of the 10-minute reading to the 1-minute reading; DAR is the ratio of the 60-second to the 30-second reading. PI requires a longer test duration but gives a more reliable indication of insulation quality. DAR is quicker. For motors, transformers, and cables where full PI testing is practical, PI is preferred. DAR is useful for a quick assessment when time is limited. Both Fluke 1550C and Kyoritsu 3125A automate these calculations.

When should I choose Kyoritsu over Fluke for insulation testing?

Choose Kyoritsu when your primary use is routine LV insulation testing to SS 638 (not medium-voltage or transformer testing), budget is a consideration, IP54 ingress protection is important for exposed site conditions, and you don't need Fluke Connect wireless data management. The Kyoritsu 3125A's 4TΩ measurement range actually exceeds the Fluke 1550C's 2TΩ range at a lower price, which is useful for assessing very high-quality insulation on new cable installations.

SAC-SINGLAS accredited laboratory mark
Written by Unitest Instruments

Unitest Instruments Pte. Ltd. is a SAC-SINGLAS accredited calibration laboratory (ISO/IEC 17025, no. LA-2023-0845-C) based in Singapore. We calibrate electrical, temperature, pressure, and related instruments (including Fluke and Kyoritsu insulation resistance testers), for M&E contractors, EMA-licensed electricians, facilities managers, and regulated industries across Singapore and the region.

Calibrate Your Insulation Tester in Singapore

Unitest Instruments provides SAC-SINGLAS accredited calibration for insulation resistance testers from Fluke, Kyoritsu, Megger, and other brands. Our calibration scope covers insulation resistance from 1MΩ to 10GΩ and test voltage accuracy. The full parameter set required for SS 638 compliance documentation.

SAC-SINGLAS Accredited · ISO/IEC 17025 · Acc. No. LA-2023-0845-C