SAC-SINGLAS Accredited ISO/IEC 17025 Acc. No. LA-2023-0845-C Traceable to Singapore's NMC View Scope
Brand Comparison

Fluke vs Chauvin Arnoux Power Quality Analyser: Which Is Right for Singapore Facilities?

Power quality analysers from Fluke and Chauvin Arnoux both dominate the professional market, but they target different use cases. Fluke's 435-II and 1760 series are widely adopted in facilities management and utility monitoring; Chauvin Arnoux's Qualistar series is especially strong in European-standard compliance measurement. For Singapore electrical engineers measuring against SS 638 (Code of Practice for Electrical Installations) and EN 50160 power quality standards, this comparison explains the key differences and which instrument best matches your application.

24 June 2026 12 min read Brand Comparison
Power quality analyser calibration in a Singapore electrical laboratory
Quick Answer For most Singapore facilities management and utility compliance applications, the Fluke 435-II remains the stronger all-round choice due to its Energy Monetization function, mature local support network, and broad SS 638 compliance toolset. However, if your primary need is rigorous EN 50160 harmonic compliance reporting with 4-channel simultaneous measurement, the Chauvin Arnoux Qualistar+ (C.A 8336) offers measurably superior harmonic analysis capabilities and a more structured European compliance workflow.

Key Takeaways

  • Fluke 435-II converts power quality events to SGD cost figures via Energy Monetization. A practical advantage for facilities managers justifying capital spend.
  • Chauvin Arnoux Qualistar+ measures harmonics to 30MHz bandwidth simultaneously across 4 channels, exceeding the Fluke's 3-channel standard configuration.
  • Both instruments require annual SAC-SINGLAS accredited calibration to maintain traceability for SS 638 compliance reporting. Calibration parameters include AC voltage, current, power/energy, and harmonic amplitudes.
  • Singapore's adoption of EN 50160 as a power quality reference means harmonic measurement to at least the 50th order is mandatory for grid compliance assessments.
  • Fluke Connect cloud logging gives the 435-II a data management advantage in multi-site facilities portfolios; the Qualistar+ records to SD card with PC software download.

Understanding Power Quality in Singapore's Electrical Landscape

Singapore's electrical infrastructure operates under a tightly regulated framework that demands precision measurement across a wide range of power quality parameters. For facilities engineers, compliance officers, and maintenance teams working in data centres, industrial plants, and large commercial developments, understanding the applicable standards is the necessary starting point before selecting any power quality instrument.

SS 638: Code of Practice for Electrical Installations is the governing standard for electrical design and installation in Singapore, maintained by Enterprise Singapore. It sets requirements for supply characteristics, protection coordination, harmonic limits, and documentation practices for new installations, major renovations, and periodic maintenance testing. Compliance documentation under SS 638 typically requires measurements traceable to a national metrology standard, which is where SAC-SINGLAS accredited calibration becomes a contractual and regulatory necessity rather than a best practice.

EN 50160 defines the voltage characteristics of electricity supplied by public distribution networks in Europe, and Singapore has progressively adopted its limits as a reference standard for power quality benchmarking. EN 50160 specifies permissible ranges and limits for power frequency, supply voltage magnitude, voltage fluctuations, voltage dips, short interruptions, temporary overvoltages, transient overvoltages, supply voltage unbalance, and harmonic voltage. For facilities that export to the grid, take supply at transmission voltage, or serve as anchor tenants in mixed-use developments, formal EN 50160 compliance reports are commonly required by SP Group, BCA, or international building owners.

The key power quality parameters that facilities engineers in Singapore must measure include:

  • Voltage magnitude and variation. The nominal supply voltage in Singapore is 230V single-phase, 400V three-phase at 50Hz. EN 50160 permits ±10% of the nominal voltage for 95% of 10-minute mean RMS values over a week.
  • Frequency. Power frequency must remain within ±0.5Hz of 50Hz for the majority of operating time under EN 50160. Singapore's grid operates at very tight frequency tolerances, making this parameter straightforward to measure but important to document.
  • Total Harmonic Distortion (THD). Harmonic distortion from non-linear loads (variable speed drives, UPS systems, LED lighting, server power supplies) is a primary concern in data centres and commercial buildings. EN 50160 limits THD to 8% of the fundamental, with specific limits for individual harmonic orders.
  • Flicker (Pst and Plt). Short-term and long-term flicker indices are required measurements where arc furnaces, welding equipment, or large motor starts are present. EN 50160 sets Plt ≤ 1.0 for weekly assessments.
  • Voltage unbalance. Three-phase systems must maintain voltage unbalance within 2% negative sequence under EN 50160. Unbalance causes motor heating, reduced efficiency, and premature equipment failure. Making it a critical parameter for industrial facilities.
  • Transients and voltage events. Voltage sags, swells, and transients are captured and characterised against EN 50160 limits and the ITIC/CBEMA curve.

For Singapore's data centres, which operate under Tier III and Tier IV uptime standards and face stringent SLA commitments to tenants, power quality monitoring is continuous rather than periodic. The economic cost of harmonic-induced losses, premature UPS failure, and unplanned downtime makes power quality instrumentation a capital expenditure that requires both technical accuracy and robust data management. Industrial facilities dealing with significant non-linear loads (plastics processing, precision machining, pharmaceutical manufacturing), face similar requirements. Large commercial buildings, meanwhile, increasingly document power quality as part of BCA Green Mark submissions and tenant energy reporting obligations.

Fluke 435-II and 1760 Series. The Facilities Management Workhorse

The Fluke 435-II is the most widely deployed professional power quality analyser in Singapore's facilities management sector, and its commercial dominance is grounded in a set of genuinely practical features rather than brand loyalty alone.

The instrument's most distinctive capability is Energy Monetization. A function unique to Fluke's power quality line that converts power quality events directly into estimated annual cost figures in the user's local currency. Rather than presenting a harmonic distortion reading of 12% THD as an abstract number, the 435-II translates that reading into a projected SGD cost per year based on power consumption, tariff rates, and the efficiency losses attributable to the distortion. For a facilities manager presenting to a board or justifying a capital replacement programme, this translation from technical measurement to business impact is a significant practical advantage. The Energy Monetization function addresses one of the perennial challenges in facilities engineering: persuading non-technical decision-makers that power quality investment has a quantifiable return.

Technically, the 435-II measures three voltage channels plus four current channels simultaneously. Its 400Hz measurement bandwidth covers the 50th harmonic at the 50Hz power frequency (2500Hz), which satisfies the EN 50160 harmonic measurement requirement. The instrument captures individual harmonic amplitudes, phase angles, and harmonic power by order, displaying results as bar charts or numerical tables against EN 50160 limit overlays. Voltage and current THD are displayed continuously.

The Fluke Connect wireless ecosystem gives the 435-II a data management capability that is particularly valuable for organisations managing multiple sites. Measurements logged on the instrument synchronise via Wi-Fi or Bluetooth to the Fluke Connect cloud platform, where they can be shared with remote engineers, archived for compliance records, or trended over time in a centralised dashboard. For a facilities team covering a portfolio of commercial buildings or industrial plants across Singapore, Fluke Connect significantly reduces the administrative burden of compiling power quality records for EN 50160 compliance reporting or maintenance contract documentation.

The 435-II carries CAT IV 600V / CAT III 1000V safety ratings. The highest safety classification for instruments working at the point of supply and in distribution systems. This rating is the appropriate category for measurements taken at incoming supply switchboards, utility metering points, and main distribution panels in Singapore's commercial and industrial buildings. The instrument is IP65 rated on the front panel, providing protection against dust ingress and water jets during site work.

For standard EN 50160 compliance surveys, the 435-II includes a dedicated EN 50160 compliance reporting mode that runs a continuous assessment against the standard's limits across all parameters. At the end of the monitoring period, the instrument generates a pass/fail summary against each EN 50160 parameter category. A report that can be exported and included in compliance documentation.

The Fluke 1760 Series addresses a different use case: long-term, unattended power quality surveys lasting weeks or months. Where the 435-II is a field instrument for spot measurements and short-term surveys, the 1760 is designed to be permanently installed at a supply point and left to log. It captures 365 days of continuous data on 8GB of internal storage, with automatic event triggering that records voltage sags, swells, transients, and interruptions as they occur without operator attendance. The 1760 is the appropriate choice for utility billing dispute resolution, equipment failure investigations requiring historical data, and long-term power quality characterisation programmes. Its higher price point (SGD 12,000–18,000 versus SGD 4,500–6,000 for the 435-II) reflects this extended capability.

Singapore engineers benefit from strong local Fluke support infrastructure. Authorised service centres, a well-stocked local distribution network for accessories and replacement fuses, and calibration support through Singapore-based service partners. For facilities teams that cannot afford extended instrument downtime, the availability of fast local repair and calibration turnaround is a practical differentiator.

Chauvin Arnoux Qualistar+ (C.A 8336). The European Compliance Specialist

Chauvin Arnoux, the French precision instruments manufacturer founded in 1893, brings a distinctive metrology heritage to the power quality analyser market. Where Fluke's strength lies in practical field usability and data management ecosystems, Chauvin Arnoux's Qualistar+ series is built around measurement precision, comprehensive harmonic analysis, and structured compliance workflows that align closely with European regulatory expectations.

The C.A 8336 Qualistar+'s defining technical capability is its 4-channel simultaneous voltage and current measurement. Where the Fluke 435-II measures three voltage channels and four current channels, the Qualistar+ measures all four voltage channels (three phases plus neutral) and all four current channels simultaneously. This matters for compliance reporting: simultaneous measurement ensures that all parameters are recorded at precisely the same instant, eliminating the timing errors that can occur when channels are sequentially sampled. For engineers producing formal EN 50160 compliance reports for regulatory submission or contractual delivery, simultaneous measurement is the technically rigorous approach.

The Qualistar+'s 30MHz measurement bandwidth is substantially wider than the Fluke's 400Hz bandwidth. At 50Hz power frequency, the 50th harmonic falls at 2500Hz, well within both instruments' capability. However, the Qualistar+'s extended bandwidth enables measurement of inter-harmonics (frequencies between integer multiples of the fundamental), sub-harmonics, and very high-order harmonics that fall above the 50th order. Inter-harmonic analysis is increasingly relevant in facilities with large-scale variable speed drive installations, where inter-harmonic injection at non-integer multiples of 50Hz can cause flicker, interference with ripple control systems, and thermal effects in transformers. The EN 50160 standard addresses inter-harmonics as an emerging parameter, and regulators are progressively tightening limits. Facilities engineers working in future-proof compliance programmes will find the Qualistar+'s extended bandwidth valuable.

The C.A 8336 is IEC 61000-4-30 Class A compliant (the same classification as the Fluke 435-II), meaning both instruments meet the measurement methodology and accuracy requirements for instruments used in formal compliance testing. The Qualistar+ is rated CAT IV 600V for supply-level measurements and carries IP54 ingress protection, positioning it for demanding site environments.

Chauvin Arnoux's structured EN 50160 compliance reporting in the Qualistar+ is arguably more fully developed than Fluke's equivalent. The instrument runs automated pass/fail assessment against all EN 50160 parameter limits and generates a structured compliance report that identifies non-conforming events, statistical summaries, and overall standard compliance status. For engineers whose primary deliverable is a formal EN 50160 compliance report (rather than a facilities management energy cost analysis), this structured workflow reduces post-processing work.

The Qualistar+ logs measurement data to a standard SD card and uses Chauvin Arnoux's DataView PC software for data download, analysis, and report generation. DataView provides comprehensive graphing, harmonic spectrum analysis, and event playback capabilities. The workflow is more traditional than Fluke Connect's cloud approach (SD card removal and PC download rather than wireless synchronisation), which may be a consideration for organisations with strict IT security policies that restrict cloud connectivity for measurement instruments.

Chauvin Arnoux instruments are available in Singapore through authorised regional distributors, with calibration and repair support through the manufacturer's Asia-Pacific service network. The local support infrastructure is less extensive than Fluke's Singapore-based presence, and facilities teams should factor potential longer calibration and repair turnaround times into their instrument management planning.

Head-to-Head Comparison Table

Parameter Fluke 435-II Fluke 1760 C.A Qualistar+ (8336)
Channels 3V + 4I 3V + 4I 4V + 4I simultaneously
Harmonic bandwidth 400Hz (50th at 50Hz) 400Hz 30MHz
Harmonic order Up to 50th Up to 50th Up to 50th + inter-harmonics
EN 50160 compliance mode Yes Yes Yes (automated pass/fail)
Energy Monetization Yes No No
Logging Internal 32MB + PC 8GB internal SD card
IP rating IP65 (front) IP41 IP54
Safety category CAT IV 600V CAT III 300V CAT IV 600V
Approx. price (SGD) $4,500–$6,000 $12,000–$18,000 $3,800–$5,200
Best for Facilities, maintenance Long-term surveys Compliance, research

SS 638 and EN 50160. What Singapore Engineers Must Measure

Understanding exactly what SS 638 and EN 50160 require in practice helps clarify which instrument specifications are genuinely necessary versus which represent capability beyond your compliance obligations.

SS 638 specifies requirements for electrical installations in Singapore covering both new installations and ongoing maintenance testing. For power quality, SS 638 references measurement requirements for harmonic distortion at points of common coupling, particularly where non-linear loads exceed threshold levels. The standard requires documentation of measured values with traceability to national standards, which in practice means calibration certificates from a SAC-SINGLAS accredited laboratory. Compliance documentation produced during periodic testing or commissioning must include measured values, instrument identification, calibration certificate reference, and the applicable limits.

EN 50160 voltage characteristic limits define the boundary conditions for acceptable supply quality. The most important parameters for Singapore facilities engineers are:

  • Power frequency: The mean value of the fundamental frequency measured over 10 seconds must be within 50Hz ± 0.5Hz for 99.5% of a year in interconnected systems. During abnormal conditions (islanding), wider limits of 47–52Hz apply.
  • Supply voltage magnitude: The mean RMS voltage measured over 10 minutes must be within ±10% of the nominal voltage (Un) for 95% of weeks. All 10-minute mean RMS values must fall within –15%/+10% of Un.
  • Harmonic voltage limits: EN 50160 Table 1 specifies individual harmonic voltage limits expressed as a percentage of the fundamental voltage. Key limits include: 3rd harmonic ≤5%, 5th harmonic ≤6%, 7th harmonic ≤5%, 11th harmonic ≤3.5%, 13th harmonic ≤3%, 17th ≤2%, 19th ≤1.5%, 23rd ≤1.5%, 25th ≤1.5%. Total Harmonic Distortion (THD, including up to the 40th harmonic) must not exceed 8%. These limits apply for 95% of 10-minute mean RMS values over a week.
  • Measurement to the 50th harmonic order: Compliance assessments must measure individual harmonic voltages to at least the 50th order (2500Hz at 50Hz) to fully characterise harmonic content as required by EN 50160 and IEC 61000-4-30. Both the Fluke 435-II and Chauvin Arnoux Qualistar+ meet this requirement; instruments with lower harmonic measurement capability cannot be used for formal EN 50160 compliance testing.
  • Flicker: EN 50160 requires that the long-term flicker severity Plt not exceed 1.0 for 95% of weekly periods. Short-term flicker (Pst) is also recorded. Flicker measurement requires IEC 61000-4-15 compliant flickermeters, which are incorporated in both the 435-II and Qualistar+.
  • Voltage unbalance: The negative sequence voltage component must not exceed 2% of the positive sequence voltage for 95% of 10-minute mean RMS values over a week. In some areas with single-phase connections, values up to 3% may occur. Three-phase facilities with unbalanced loads (a common condition in commercial buildings with mixed single-phase and three-phase loads), must monitor this parameter continuously.

For Singapore engineers, the practical implication is clear: any power quality analyser used for formal SS 638 or EN 50160 compliance documentation must measure harmonics to at least the 50th order, capture flicker, measure voltage unbalance as a negative sequence percentage, and record power frequency. Both the Fluke 435-II and Chauvin Arnoux Qualistar+ satisfy all of these requirements. The difference lies in how comprehensively they handle inter-harmonics (advantage: Qualistar+) and how they translate results into compliance reports and business-case documentation (advantage: Fluke 435-II for Energy Monetization, Qualistar+ for structured EN 50160 pass/fail reporting).

Calibration Requirements for Power Quality Analysers

Both the Fluke 435-II and Chauvin Arnoux Qualistar+ require annual calibration to maintain metrological traceability for use in compliance documentation. This is not merely a manufacturer recommendation. It is a practical requirement when measurement results are used to support regulatory compliance, contractual deliverables, or legal dispute resolution. A power quality report produced with an instrument operating outside its calibrated specification has limited evidential value if challenged.

The parameters that must be calibrated for a power quality analyser to be fully fit for EN 50160 and SS 638 compliance testing are more extensive than many facilities teams realise:

  • AC voltage measurement (true RMS): The instrument must be calibrated for AC voltage accuracy across the full range of input voltages from below nominal to the maximum expected supply voltage, at the fundamental frequency (50Hz). True RMS measurement accuracy must be verified. Instruments that measure only average-responding voltages with an RMS scale factor will misread distorted waveforms.
  • AC current measurement: Current measurement accuracy must be verified for the specific clamp accessories used with the analyser, as clamp accuracy significantly affects power and energy measurement results. Clamps must be calibrated separately from the instrument body or as part of a system calibration that includes the clamp.
  • Power and energy parameters: Active power (W), reactive power (VAr), apparent power (VA), and energy (kWh) must be calibrated, as these parameters are derived from the voltage and current measurements and their phase relationship. Energy Monetization results are only meaningful if the underlying power measurements are traceable.
  • Harmonic amplitude by frequency band: This is the calibration parameter most frequently omitted by non-accredited calibration providers. Harmonic measurement accuracy must be verified at multiple frequency points across the instrument's measurement range. Typically at the 3rd, 5th, 7th, 11th, 13th, 17th, 19th, 23rd, 25th, 29th, 35th, and 50th harmonic frequencies at minimum. A calibration certificate that covers only fundamental frequency (50Hz) AC voltage and current provides no assurance of harmonic measurement accuracy, which deteriorates at higher frequencies due to bandwidth limitations, anti-aliasing filter roll-off, and input impedance effects.
  • Harmonic uncertainty at higher frequencies: Measurement uncertainty for harmonic amplitudes increases with frequency. A calibration certificate from an accredited laboratory will state expanded uncertainty values for harmonic measurements at each calibrated frequency. Information that is necessary for compliance engineers to assess whether the instrument's measurement uncertainty is compatible with the EN 50160 harmonic limits they are measuring against. For 50th harmonic measurements, expanded uncertainty values of 1–3% are typical for IEC 61000-4-30 Class A instruments.

SAC-SINGLAS accredited calibration provides metrological traceability through an unbroken chain of calibrations to Singapore's National Metrology Centre (NMC) at A*STAR. For SS 638 compliance documentation, calibration certificates from SAC-SINGLAS accredited laboratories are the recognised standard of evidence for measurement traceability in Singapore. International equivalence is maintained through ILAC mutual recognition arrangements, so SAC-SINGLAS certificates are also accepted internationally. An important consideration for facilities that form part of multinational corporate portfolios.

When requesting calibration for a power quality analyser, facilities engineers should explicitly verify that the provider's accreditation scope covers harmonic amplitude measurements. An accreditation schedule that lists only "AC Voltage" and "AC Current" at the fundamental frequency does not cover harmonic calibration. Request the provider's SAC-SINGLAS accreditation schedule and confirm that harmonic parameters are explicitly listed before proceeding.

Accredited Calibration

Calibrate Your Power Quality Analyser to SAC-SINGLAS Standards

Unitest Instruments provides SAC-SINGLAS accredited calibration for Fluke and Chauvin Arnoux power quality analysers. Our calibration certificates include explicit harmonic amplitude calibration. The parameter most often omitted by non-accredited providers.

Which Should You Choose?

The right instrument depends on your primary use case, your reporting obligations, and your organisation's operational context in Singapore. The following guidance covers the three main scenarios.

Choose the Fluke 435-II if:

  • Your primary role is facilities management. Building operations, plant maintenance, or tenant power quality monitoring where Energy Monetization reports help you justify expenditure to non-technical stakeholders.
  • You need multi-site data management. Fluke Connect's wireless synchronisation and cloud dashboard make the 435-II significantly more productive for organisations managing multiple buildings or industrial sites across Singapore.
  • Local service support is a priority. Fluke's Singapore authorised service network offers faster repair turnaround and local spare parts availability compared to Chauvin Arnoux's regional service infrastructure.
  • Your compliance work spans both SS 638 and EN 50160 without requiring inter-harmonic analysis or 4-channel simultaneous measurement. The 435-II satisfies both standards' core measurement requirements.
  • You already operate in the Fluke ecosystem with clamp meters, insulation testers, and thermal cameras on Fluke Connect. The 435-II integrates naturally into an existing Fluke infrastructure.

Choose the Fluke 1760 if:

  • You need long-term unattended power quality surveys lasting weeks or months. Utility billing disputes, equipment failure root-cause investigations, or power quality characterisation programmes for new developments require the 1760's 8GB continuous logging capability.
  • Automatic event capture without operator attendance is required. The 1760 triggers and timestamps voltage sags, swells, transients, and interruptions automatically, building a complete power quality event record without field personnel present.
  • You are conducting utility-level monitoring contracts that require comprehensive historical datasets for regulatory reporting or dispute resolution with SP Group.

Choose the Chauvin Arnoux Qualistar+ (C.A 8336) if:

  • EN 50160 compliance reporting is your primary deliverable. The Qualistar+'s automated pass/fail EN 50160 compliance reporting is more fully structured than the 435-II's equivalent, reducing post-measurement analysis work when the final output is a formal compliance certificate.
  • Inter-harmonic analysis is required. Facilities with large VSD installations, arc furnaces, or other inter-harmonic-generating loads need the Qualistar+'s 30MHz bandwidth to fully characterise power quality and assess EN 50160 inter-harmonic compliance.
  • 4-channel simultaneous measurement is specified in your measurement protocol or client contract. Simultaneous measurement of all four voltage and current channels provides the highest technical rigour for compliance reporting.
  • Budget is tighter than the Fluke 435-II, at SGD 3,800–5,200, the Qualistar+ is modestly less expensive than the 435-II while offering superior harmonic analysis capability.
  • Your organisation operates primarily in European regulatory environments. The Qualistar+'s French metrology heritage and LCIE calibration traceability align naturally with European-standard compliance workflows.

Frequently Asked Questions

Which power quality analyser is better for SS 638 compliance testing in Singapore?

Both the Fluke 435-II and Chauvin Arnoux Qualistar+ meet the core measurement requirements for SS 638 compliance. The Fluke 435-II has a slight edge for general facilities compliance due to its Energy Monetization function and mature Singapore support network. However, if your primary deliverable is a formal EN 50160 compliance report with automated pass/fail assessment against all standard limits, the Qualistar+'s structured EN 50160 reporting mode is more comprehensive out of the box.

What is the measurement accuracy difference between Fluke and Chauvin Arnoux power quality analysers?

Both instruments are IEC 61000-4-30 Class A compliant, which defines the measurement accuracy and methodology requirements for power quality instruments used in compliance testing. At the fundamental frequency (50Hz), accuracy differences between the two brands are minimal, both achieve better than ±0.1% for voltage magnitude. The key difference emerges at higher harmonic frequencies, where the Qualistar+'s 30MHz bandwidth provides more accurate measurement of higher-order harmonics compared to the Fluke's 400Hz bandwidth.

Can the Fluke 435-II measure harmonics to the 50th order?

Yes. The Fluke 435-II measures voltage and current harmonics to the 50th order (2500Hz at 50Hz fundamental), which is the standard requirement for EN 50160 compliance. For inter-harmonics or sub-harmonics, or for applications requiring measurement beyond the 50th order, the Chauvin Arnoux Qualistar+ with its 30MHz bandwidth offers broader coverage.

What local support is available for Chauvin Arnoux instruments in Singapore?

Chauvin Arnoux instruments are available through authorised distributors in Singapore, with calibration and repair support through regional service partners. However, the local support infrastructure is less extensive than Fluke's, which has a directly authorised service and calibration network in Singapore. For facilities teams requiring fast turnaround on instrument repair and calibration, Fluke's local presence is an advantage.

How often do power quality analysers need calibration?

Annual calibration is the standard recommendation for power quality analysers used in compliance testing. The calibration interval should be formally documented in your measurement management system. If an instrument is dropped, subjected to excessive voltage transients, or shows inconsistent readings, out-of-schedule calibration is warranted regardless of the annual cycle.

When should I choose the Fluke 1760 over the 435-II?

The Fluke 1760 is designed for long-term unattended power quality surveys. It can log continuously for weeks or months with automatic event capture triggered by power quality anomalies. If you need to characterise power quality over time (for utility billing disputes, equipment failure investigations, or power quality audits requiring seasonal data), the 1760 is the appropriate choice. For spot measurements and routine facilities surveys, the 435-II is more practical and cost-effective.

Does SAC-SINGLAS accredited calibration cover harmonic measurements?

This depends on the accreditation scope of the calibration provider. At Unitest Instruments, our SAC-SINGLAS accredited calibration for power quality analysers explicitly includes harmonic amplitude calibration by frequency band. Not just fundamental frequency voltage and current. When requesting calibration, always verify that the provider's accreditation schedule covers harmonic parameters. A calibration certificate that only covers fundamental frequency AC voltage and current does not confirm harmonic accuracy, which is a critical parameter for EN 50160 compliance testing.

Unitest Instruments
Reviewed by the Unitest Technical Team

This article was reviewed by Unitest Instruments' calibration engineers, a SAC-SINGLAS accredited laboratory (Acc. No. LA-2023-0845-C) specialising in electrical and electronic instrument calibration. Our team calibrates power quality analysers, multimeters, oscilloscopes, and RF instruments for Singapore's industrial, defence, and utilities sectors.

Need Your Power Quality Analyser Calibrated?

Unitest Instruments provides SAC-SINGLAS accredited calibration for power quality analysers, including Fluke and Chauvin Arnoux instruments. Our scope covers AC voltage, current, power, energy, and harmonic amplitudes. The full parameter set required for EN 50160 compliance documentation.

SAC-SINGLAS Accredited · ISO/IEC 17025 · Acc. No. LA-2023-0845-C